Selected Electrical Question And Answer for MEO Class 2 (3)

(a)                Give a brief outline of the care and maintenance that should be given to the stator and rotor of an AC generator.                                                                                (6m)

(b)        State what is likely to occur if the driving power of an AC generator suddenly fails when two generators are operating in parallel.                                        (4m)

Answer :-

(a)                Before any generator work can be carried out:
1)      prime mover must be shut down and secured.
2)      Generator circuit breaker is locked off.
3)      Generator electric heaters isolated.
Maintenance that should be given to the stator and rotor of an AC generator:
1)      check all wiring for damaged or fractured. Check for sign of water and oil contamination of cable.
2)      Check cooling air intake and exhaust are free from dirt and dust.
3)      Inspect and clean generator rotor and stator windings.
4)      Check insulation and tightness of terminal insulation correction.
5)      For generator with slip rings, it must be checked for even wear and carbon brushes for free movement. Correct brush pressure can be checked by pull type spring balance.
6)      Replace brushes if faulty are bed in the slip ring curvature with glass paper. Clean dusty area with vacuum cleaner after bedding.
7)      For brushless generator, check excitation transformer, AVR components and rotating diodes for oil and dirt.
8)      Measure insulation of the stator and rotor windings to earth and between stator phases.
9)      After maintenance carry out, run on no load. If all OK, check on load foe excessive temperature rise and load sharing stability when running in parallel.


(b)               When prime mover of a generator fails while it is running parallel with another, the generator of the failed prim mover acts as synchronous motor placing additional load on the other generator.
At the preset value, reverse power protection detects this faults and trips failed generator circuit breakers.