(a)
Briefly describe how a running AC generator would be
taken off load and another generator put on load without a blackout. (3m)
(b)
State the danger arising from reducing the excitation
of the outgoing generator before it is off loaded. (4m)
(c)
State what would be the effect on the current, voltage
and frequency of the machine if an AC generator allowed down slightly during
operation. (3m)
Answer :-
(a)
The incoming generator is synchronised with the running
generator after having ensure that the frequency and voltage of both generators
are identical, both having the same phase sequence and the phase angle
difference between the voltage is zero. To minimise the possibility of
blackout, both generator should be allow to run in parallel for a short time
before taking the outgoing are off load.
(b)
When the excitation of the outgoing generator is
reduced, the current taken by it is reduced. The current (load) of the other
generator is thus increased and if exceed the rated current, the overload relay
will trip the generator and a blackout would occur.
(c)
If one machine running alone:
1) speed
slow down, frequency decreases. N a f/p.
2) Voltage
is not affected as it controlled by AVR.
3) Impedance
reduces (XL = 2PfL)
with voltage being constant, current would therefore increase.
If two alternators in parallel:
If one generator slow down
slightly, it would drop / shed part of its kW loading which would be taken up
immediately by the other one. However, there will be no change in the
frequency, voltage and current in the system as both are locked electrically.
No comments:
Post a Comment