menu 2

Drop Down MenusCSS Drop Down MenuPure CSS Dropdown Menu

Friday, November 6, 2015

Selected Electrical Question And Answer for MEO Class 2,,,,,,,, 01

(a)        Explain why it is not goo practice to replace only single fuse in a 3 phase motor and why fuse clips and connections need examination during fuse renewal.  (5m)

(b)        State the main difficulty as to why an overload protection for an AC motor current be set fairly low, and what is done to overcome this difficulty.                               (5m)


Answer :- 

(a)                It is not a good practice to replace only a single fuse in a three phase motor because:
1)      due to aging of the fuses and cause dampness of the fuse.
2)      Material properties f the fuse will be weakened due to expose to the increased current.
3)      Rating will be drop and could operate at a much lower operating value than it was originally designed.
Thus the loss of machinery during normal operation could occur and it could be dangerous if it were on essential service equipment. As we know, burnt of one fuse can cause single phasing resulting the current in the energised winding approx. to double. Frequent single phasing can damage the respective machinery which is unsafe while operating.
Fuse clips and connections should be examined when renewing fuses as a scored contact may cause, operation below the correct value due to being oxidised, melted or weakened by the high current.

(b)               The main difficulty as to why an overload protection for an AC motor cannot be set fairly low because :
1)      direct on line starting for motors causes an initial rushing of starting current that is 5 to 8 times of full load current. Thus the protective device must be  inoperative during the starting periods but operative on normal moderate overloads, on short circuit and during stalled condition.
2)      similarly same motors with starting sequence that requires an initial current of 15% to 20% overload at short time interval, requires that the overload device will not trip the motor when a high starting current before the starting operation has completed.
The methods to overcome this problems are:
1)      to leave the relay out of circuit until the starter is in the running condition. this is done for centrifuge driver which have considerable inertia and long starting times of the operation of 45 to 60 secs. Thus time delay or relay units that have a variable time features are incorporated.
To feed the relays from the current transformers having magnetic circuits designed to become saturated at about 2 to 4 times of full load current. Although the line current may exceed these values, the current in the relay coil will be restricted.   


(a)        Explain why it is important to ensure that supply connections to a three phase motor are made in the correct order.                                                                           (2m)

(b)        Explain how the correct order of phase connection from three phase supply lines to motor terminals can be deduced from standard markings, and state a necessary precaution in guarding against incorrectly marked terminals.                     (4m)

(c)        Describe the effect of running a motor with the stator windings connected in star when the motor is designed for running with delta connected windings.   (4m)


Answer :-

(a)                It is important to ensure that the supply connections to a three phase motors are made in the correct order so that :
1)      to ensure that the direction of motor is correct before couples to a machinery, otherwise damage may be done to the driven machinery e.g. electro hydraulic steering pumps.
2)      In case of lifts, hoists, all electric steering gear, the limit switches may not afford protection. It the lift travels up, instead of down, the top limit switch may open control circuit, which is not energised and the motor will not stop.

(b)               Standard markings with British Standard, if generator is driven with clockwise rotation when looking at its driven end, the terminal phase sequence will be in the order A, B, C. (For colour marking, the sequence in Red, Yellow, Blue). If the motor is connected to a supply terminal phase sequence in the order of A,B,C, then the motor would rotate in clockwise direction.
A necessary precaution is guarding against incorrectly marked terminal is by run the motor with coupling to mechanical equipment disengaged. Ensure correct running direction. In case of air compressor if wrong direction, compressed air still can be produced but lub oil pump engaged to compressor will not working, no lubrication cause bearing damage.

(c)                The effect of running a motor with stator windings connected in star when the motor is designed for running with delta connected windings are :
1)      a star delta motor starter gets stuck in star position, malfunction in control timer, contactors, etc.
2)      On full load, each stator winding will be carrying an overload of 1.73 x rated line current.
3)      This will cause overheating, because of I² R effect. The motor will run 3 times hotter.
4)      But the line current will be normal and thermal overload protection will not protect the motor. This will cause overheating and eventually burn out.

The vessel you have joined has AC alternators generating a voltage of 3.3 kV to the main switchboard. Discuss after an inspection of the main switchboard, how would you :
           
(a)                control access to the live busbars or circuits, for purposes of inspection or maintenance.                                                                                         (2m)
(b)               Precautions to be taken before work commence on any unprotected bus bar or circuit.                                                                                            (4m)
(c)                What information would you require to be included in a ‘permit to work’ authorisation form.                                                                                (4m)

Answer :-

(a)                Control and access to the live bus bars of circuit for inspection or maintenance:
1)      barriers circuit of access to enclosures containing high voltage conductors shall kept locked. Only authorised personal shall have access to such enclosures.
2)      Working plate, entry ways kept clear and free of obstruction.
3)      Portable tools used should be earthed or double insulated.
4)      Prevent ingress of moisture, dirt, foreign matters into electrical equipment, when work is in progress, cover should be closed as soon as access is not required.


(b)               Precautions to be taken before work commence on any unprotected bus bars or circuit.
No person should undertake repair, maintenance, cleaning of high voltage system unless such parts are :
1)      isolated locked off, fuses removed, circuits such as alarms, interlocks, heating and lighting may still be alive, receiving power from other source (reverse energising of transformer and open circuit of current transformer secondary coil is a hazard).
2)      Dead voltage indicator must be proves before and after this test.
3)      Permanently display caution notices.
4)      All phases of dead circuit are earthed.
5)      Screen where necessary to prevent danger – on live circuit nearby.
6)      Permit to work is issued.
7)      Person is competent to do the work.

(c)                Information that C/E should give :
1)      items on which you are to work on.
2)      Points on which system is isolated.
3)      Caution notice posted.
4)      Earthing of apparatus.
5)      Who to carry out the job.
6)      What work to be done.

To give:
1)      time and date of work to carry out.
2)      Time and date of completion.
3)      C/E and E/E to sign signature.

On medium voltage, 440V marine, AC, 3 phase, distribution system, the neutral wire is invariably insulated, whereas in shore practice it is otherwise. Briefly list and give reasons for :
           
            (a)        the advantages of insulating the neutral, and                                     (5m)

            (b)        the disadvantages of insulating the neutral.                                       (5m)

Answer :-

(a)                Advantages of insulating the neutral:
1)      protect the essential service in case of earth fault occurred.
2)      Less fire risk.
3)      Less prone to single phasing.
4)      No danger of triple current (3rd harmonic current), overheat will activated earth fault relay which may trip off the generator.

(b)               Disadvantages:
1)      earth fault detection harder.
2)      Phase voltage at line voltage (if one phase earthed, insulation highly stressed due to star connected).
3)      Less suitable in high voltage system.
4)      Required step down transformer, double pole switches/fuses for/and lower voltage sub circuits.
5)      Subjected to over voltage due to seasoned or intermittent fault. 


            With respect to silicon rubber insulated cables briefly discuss :

            (a)        its advantages                                                                                     (6m)

            (b)        its disadvantages.                                                                                (4m)


Answer :-

(a)                Advantages of silicon rubber insulated cables:
1)      silicon rubber has outstanding resistance to high temperature.
2)      It can continuously operate at temperature up to 150ºC.
3)      In case of fire, it burns to form silicon oxide which is an electric insulators. Hence, operation can continue even after a fire, provided conductor is not melted.
4)      It is not mechanically robust, but remains flexible down to very low temperature.
5)      However, modern grade has adequate mechanical strength to withstand rough handling.

(b)               Disadvantages:
1)      not oil resistant. Hence sheathing of glass braiding with heat resisting varnish needed.
2)      It is very expensive and only used for special applications.

  



No comments:

Post a Comment