menu 2

Drop Down MenusCSS Drop Down MenuPure CSS Dropdown Menu

Friday, January 13, 2017

Oral question bank with answer for MEO Class-2&3



What is a thermostatic expansion valve?

This is a regulator through which the refrigerant is metered from the high pressure side to the low pressure side of the system. The pressure drop causes the evaporating temperature (saturation temp.) of the refrigerant to fall below that of the evaporator.
a.         Avoids liquid refrigerant return to the compressor suction.
b.         Automatic expansion control and maintain 6 ~ 7 degree superheat.

7.         What is a Coalescer?

A device consisting of a material whose surface provokes coalescence. The process of combining of larger droplets of a liquid like oil into larger droplets is called coalescing.


8.         Why is there a starting air overlap provided in a diesel engine?

a.         To give a positive starting in correct direction.
b.         Starting ability from any position.
c.         If any one of the valve is malfunctioning, Engine can still be started.

9.         What is the significance of firing order?

a.         Balancing of primary and secondary inertia forces.
b.         To assist the exhaust grouping.
c.         For distribution of stress over the length of crankshaft and optimum bearing loading.
d.         A firing interval for even turning moment.


11.       Explain the functions of lube oil in refrigeration system

a.         Lubrication
b.         Seal the clearance spaces between the discharge and suction sides of the compressor.
c.         Act as a coolant.
d.         Actuate capacity control.
e.         Dampen the noise generated by the compressor.



12.       What are the various windlass safeties?

ELECTRIC:   
a.         Electromagnetic brake.
b.         Motor overload protection.
c.         Short circuit protection.
d.         Restart delay timer.
e.         A Restart stop.
MANUAL:
a.         Manual brake / mech. Brake.
b.         Cable stopper.
c.         Slipping clutch (torque limiter).
d.         Relief valve.

13.       What are the steering gear motor safeties?

a.         Overload alarm.
b.         200% insulation in motor.
c.         High temperature alarm.
d.         Self starting after power failure.
e.         Short circuit trip.
f.          If the ship has an earthed neutral, then the motor neutral is earthed through a transformer.
g.         Phase failure alarm.
h.         One of the steering motor is fed from the emergency bus.

Hydraulic side there is two trips
a.         Low level cutout
b.         High lube oil temperature cutout.

14.       What are the overhead crane safeties?

Current to motor's field coils passes through solenoid coil of a brake which is magnetized and holds a brake against spring and releases the rotor. Incase of power failure the solenoid is demagnetized and brake is applied.

SAFETY:
a.         Limit switch on the f'wd, aft, port, s'tbd, hoisting and lowering prevents movements more than the allowed limits.
b.         Overload trip.
c.         Dead man's handle.
d.         Guards over the pulley.
e.         Locking device on the lifting hook.
f.          Mechanical locking (to avoid crane movement during heavy weather)

15.       What is a critical pressure?

It is the pressure at which gas will just liquefy at its critical temperature.

16.       What is a critical temperature?

It is the temperature above which the gas cannot be liquefied under isothermal compression.



17.       What are the air bottle safeties?

a.         Relief valve
b.         Fusible plug
c.         Drain
d.         Low pressure alarm

20.       What are the causes of turbocharger surging?

a.         Rapid variation (reduction) in load.
b.         Chocked exhaust and air passage like scavenge ports, valve or air cooler etc.
c.         Abnormal fuel system like a unit misfiring.
d.         Chocked air suction filter, fouling of the turbocharger, unbalanced output from the engine, damaged exhaust valve, scavenge fire.

22.       What is the normal relief valve setting of cylinder head in a diesel engine?

10 ~ 14.5% more than the working pressure. about 120 bar (some what higher than maximum pressure)

23.       State the advantages of uniflow scavenging

a.         Simple liner construction
b.         Long skirt (for piston) not required
c.         Stroke length can be increased
d.         High scavenging efficiency
e.         High thermal efficiency
f.          Low grade of fuel can be burnt
g.         Uniform wear of piston rings and liner
h.         Less thermal stresses
i.          Less intermixing of scavenging air with the exhaust gas
j.          Exhaust valve can be made to open late - more work, close early - scavenge air is more utilized.

28.       What are the reasons for black smoke from a diesel engine?

a.         Poor combustion due to faulty injection system
b.         Low compression
c.         Insufficient scavenging air
d.         Fouled exhaust system
e.         Broken piston rings
f.          Ineffective lube oil seal
g.         After burning, bad fuel and other fuel assisted faults
h.         Faulty cylinder lubrication
i.          During starting, it is inevitable as the engine maker sets the starting fuel index to a fixed value. At this index there is insufficient air, low piston speed, cold combustion chamber, low fuel injection pressure etc., each compounding the cause for black smoke

29.       What are the critical speed effects?

Resonance, Torsional vibration, fatigue failure of components

Can be remedied by:
a.         Detuners
b.         Vibration dampers
c.         Electric vibration compensator unit


33 what is critical speed?

Critical speed is when the natural frequency matches the operating frequency.

30.       What are the types of vibration in a diesel engine and which is the most damaging?

Types of vibration:
a.         Linear vibration
b.         Torsional vibration
c.         Resonant vibrations involving any two of the above or may be combinational


48.       Why are the CO2 bottles provided with dip tubes?

It is to ensure that only liquid is drawn during release. The liquid expands after the nozzles and assumes the gaseous state. This will prevent co2 freezing and blocking the nozzle
Also it achieves the 85% discharge in 2 Minutes as liquid part represents a large volume of gas
The materials used in its construction are copper, stainless steel

51.       What are the causes of a centrifugal pump reduced output?

a.         Friction and leakage losses, loss of suction head, chocked suction filter, worn out wear ring, air ingress in the suction side
b.         Low voltage is applied to the pump motor
c.         Cavitations on the impeller
d.         Bad maintenance, incorrect fixing up of the parts after overhaul

59.       What is the function of the driers in the refrigeration system?

The filter/drier is installed in the main liquid line of the system to absorb any moisture present in the refrigerant. It consists of activated alumina or silica gel in a renewable cartridge. It also accommodates the charging connection


65.       What are the advantages and disadvantages of the synthetic lube oils?

Advantages:
a.         Better low temperature fluidity and pump ability,due to nil wax content
b.         Better oil retention at high temperatures
c.         Lower friction losses
d.         Reduced thickening of the oil in service due to oxidation
e.         Lower deposits at higher temperature due to resistance to oxidation properties and thermal stability

Disadvantages:
a.         Increased cost of the lube oil (about 6~12 times)
b.         Poor availability
Uses:
a.         Air compressors
b.         Purifiers
c.         Hydraulic units


74.       What are the environmental problems with the use
of CFCs?

a.         CFC released into the atmosphere are broken down by
pyrolysis to release chlorine atoms which
catalytically destroy ozone layer.(this layer in the
stratosphere acts as a filter to the UV radiation from
the sun)
b.         Furthermore CFCs along with other greenhouse gases
inhibit radiation from the earth's surface thereby
contributing to the global warming.



78.       Why intercooling is provided in an air compressor?
And why is the compression distributed into stages?

a.         By employing the interstage cooling we are trying
to achieve an isothermal compression cycle. So least
work is expended in the process.
b.         The air outlet temperature after compression is
lowered by intercooling. So oxidation of the lube oil
is prevented. Also good lubrication is achieved.
c.         Lesser deposits in the air system.
d.         Intercooling increases the air density and hence
reduced volume of the HP compression chambers is
possible.
e.         It facilitates removal of moisture by condensation
at the intercoolers.
f.          To facilitate intercooling the compression is
distributed into stages. Also even load distribution
is achieved over the cycle.



89.       What are the safeties in the fridge system?

a.         HP cut out
b.         Differential lube oil pressure cutout
c.         LP cutout
d.         Relief valve in the condenser
e.         Belt driven
f.          Cylinder head relief valve
g.         Cooling water low flow/high temperature alarm
h.         Motor overload
i.          Oil separator
j.          Drier
k.         Mech. Seal
l.          Unloaders /capacity controllers
m.        Non return shut off valves
n.         Sensors - temperature, pressure


PROCEDURE OF BUNKERING

Before bunkering

The engineer in charge normally 3rd Engineer should give all tank soundings to the Chief Engineer.
The bunker tanks to be filled should be emptied i.e. the remaining fuel to be transferred to settling tank or unused bunker tank to prevent mixture of bunker. This is because the properties of the bunker received are not always the same.
The valves in the bunker pipeline should be set/open – made ready.
Duties divided among engine personnel i.e. Oiler, Junior Rating, 2 Engine Cadets and Duty engineer.
SOPEP- (Ship Oil Pollution Emergency Plan) items to be prepared as standby at the bunker manifold i.e. SOPEP drum, Wilden pump with hose attachments to suck the spillage, saw dust, rags, OSD- (Oil Spill Dispersant) Chemical and a 9 Litres Foam Type Portable Fire Extinguisher.

During bunkering

Ensure that the scuppers are plugged
Someone should be on standby at the manifold to look out for leakage, usually cadets.
Sounding of tanks should be taken at constant intervals, usually by Oiler.
The engineer in charge will be controlling valves if there’s a need to change tanks.
The stability is taken into account when receiving bunker.
The most important of all is that the sample of bunkered oil is taken by using a special flange called “Continuous Drip Sampling Flange”.

After bunkering

The final sounding should be taken and the amount of bunker received to be calculated.
The engineer in charge should go to the bunker barge and check all the tanks.
When everything is satisfactory, the Chief Engineer will sign on the bunker document from the bunker barge.
Ensure that the blank flange on the bunker manifold is tightly bolted.



How do you detect fire on board (In engine room and accommodation.)?

-           smoke detector
-           flame detector
-           Heat detector.

HOW TO HANDLE FIRE

F – Find
I – Isolate
R – Report
E – Extinguish

FIRE DETECTION SYSTEM

Smoke detector (Photo-electric cell)
When smoke detected, light scattered around the barrier on to the photo-cell and an alarm is triggered.

Flame Detector (infra Red)
-           Flickering radiation from flame reach the detector lens/filter unit, which allow infra-red ray to pass and focused upon the cell and then trigger the alarm.
Heat Detector (Bi-metal coil)
-           When 2 metal strip bent forward the contact point that caused by different kind of metal used in the strip when react to heat.




FIXED FIRE FIGHTING SYSTEM
FIRE MAIN
The diameter of the fire main is to be based on the required capacity of the fixed main fire pump(s) and the diameter of the water service pipes are to be sufficient to ensure an adequate supply of water for the operation of at least one fire hose.

The wash deck line may be used as a fire main if the requirements of this sub-Section are satisfied. All exposed water pipes for fire-extinguishing are to be provided with drain valves for use in frosty weather. The valves are to be located where they will not be damaged by cargo.

When the fixed main fire pump is delivering the quantity of water required , or the fire pump described as the alternative the portable pump , through the fire main, fire hoses and nozzles, the pressure maintained at any hydrant is to be sufficient to produce a jet throw at any nozzle of not less than 12 m.

CARBON DIOXIDE SYSTEM

Carbon dioxide systems are to comply with 7.1 in addition to the remaining requirements of this sub-Section. For the purpose of this Chapter, the volume of free carbon dioxide is to be calculated at 0.56 m3/kg.

For machinery spaces:
The quantity of carbon dioxide carried is to be sufficient to give a minimum volume of free gas equal to the larger of:
30 per cent of the gross volume of the largest machinery space protected, including the casing;
The fixed piping system is to be such that 85 per cent of the gas can be discharged into the space within two minutes; and
The distribution arrangements are to be such that approximately 15 per cent of the required quantity of carbon dioxide is led to the bilge areas.
Two separate controls are to be provided for releasing carbon dioxide into a protected space and each is to ensure the activation of the alarm. One control is to be used to discharge the gas from its storage cylinder(s). A second control is to be used for opening the valve of the piping, which conveys the gas into the protected space. The two controls are to be located inside a release box clearly identified for the particular space.

If the box containing the controls is to be locked, a key to the box is to be in a break-glass type enclosure conspicuously located adjacent to the box. There is to be a dedicated release box for each protected space, in which personnel normally work or to which they have access, see also 7.1.7.
The space served is to be identified at the release box. Distribution pipes for carbon dioxide are not to be smaller than 20 mm bore.

High-expansion foam systems
Any required fixed high-expansion foam system in machinery spaces is to be capable of rapidly discharging through fixed discharge outlets a quantity of foam sufficient to fill the greatest space to be protected at a rate of at least 1 m in depth per minute. The quantity of foam-forming liquid available is to be sufficient to produce a volume of foam equal to five times the volume of the largest space to be protected.

The expansion ratio of the foam is not to exceed 1000 to 1. Alternative arrangements and discharge rates will be permitted if equivalent protection is achieved. Supply ducts for delivering foam, air intakes to the foam generator and the number of foam-generating units are to be such as will provide effective foam production and distribution.

The arrangement of the foam generator delivery ducting is to be such that a fire in the protected space will not affect the foam-generating equipment.
The foam generator, its sources of power supply, foam-forming liquid, and means of controlling the system are to be readily accessible and simple to operate and are to be grouped in as few locations as possible at positions not likely to be cut off by fire in the protected space.

Foam concentrates carried for use in fixed foam fire-extinguishing systems are to be of an approved type. They are to be tested at least twice during each five-year period to verify that they remain fit for service. Evidence in the form of a report from the foam manufacturer or an independent laboratory will be accepted.
Pressure water-spraying systems
Any required fixed pressure water-spraying fire-extinguishing system in machinery spaces is to be provided with spraying nozzles of an approved type. The number and arrangement of the nozzles is to be such as to ensure an effective average distribution of water of at least five litres per square metre per minute in the spaces to be protected. Where increased application rates are considered necessary, these will be specially considered. Nozzles are to be fitted above bilges, tank tops and other areas over which oil fuel is liable to spread and above other specific fire hazards in the machinery spaces.

The system may be divided into sections, the distribution valves of which are to be operated from easily accessible positions outside the spaces to be protected and which are not to be readily cut off by fire in the protected space.
The system is to be kept charged at the necessary pressure, and the pump supplying the water for the system is to be put automatically into action by a pressure drop in the system.

The pump is to be capable of simultaneously supplying, at the necessary pressure, all sections of the system in any one compartment to be protected. The pump and its controls are to be installed outside the space(s) to be protected. It is not to be possible for a fire in the space(s) protected by the water-spraying system to put the system out of action.

The pump may be driven by independent internal combustion type machinery, but if it is dependent upon power being supplied from the emergency generator, that generator is to be arranged to start automatically in case of main power failure so that power for the pump required by 7.4.5 is immediately available. When the pump is driven by independent internal combustion machinery, it is to be so situated that a fire in the protected space will not affect the air supply to the machinery.

Precautions are to be taken to prevent the nozzles from becoming clogged by impurities in the water or corrosion of the piping, nozzles, valves, and pump. As an alternative to 7.4.1 to 7.4.7, the arrangement described in MSC/Circ.668, and amendments thereto contained in MSC/Circ.728 will be accepted or equivalent.

THE BA SET

-           Consist of an air cylinder mounted on a plastic back plate fitted with harness
-           A moulded rubber face mask incorporated demand valve, exhalation valve/speech transmitter, head harness & visor is connected by high pressure reinforced hose from the demand valve to the air manifold
-           A pressure gauge & a low pressure warning whistle which give audible warning to the wearer when 80% of the air has been used and this complete the assembly of the BA set
-           To put into operation the cylinder valve is opened & the wearer breadth, the demand valve supplies air according to his requirements at a reduced pressure irrespective of the work load

CHARGING BA SET

Recharging cylinder to, appropriate pressure as stamped on cylinder. It is only permissible to fill compressed air cylinder which:

Conform to Notional Standard in force within country of use.
Are stamped with test date and test mark of inspection authority.
Have not exceeded test interval indicated on cylinder.
Do not show signs of damage or corrosion, which could be a potential hazard, and that cylinder, is in good condition.
Do not show any signs of moisture (water droplet) in threaded connection.

Note:
Observe the following, to avoid high, water content of breathing air in compressed air cylinder:

Compressed air cylinders must not be completely emptied (depressurize) when used with compressed air respiratory protection equipment.
Maintain above atmospheric pressure after use. If however cylinder is completely emptied, ensure that cylinder valve is closed.
Cylinder valve outlet should be protected against ingress of dirt and moisture at all times i.e. after removal from compressed air respiratory protection equipment, and fit
Protective cap immediately must be protected against impact and heat when transported.

CAUSES OF OIL OVERFLOW FROM PURIFIER

-           Wrong temperature & viscosity of the oil’
-           Density of the oil not suitable
-           Using wrong gravity disc
-           Speed of the purifier too slow
-           Bowl stuck open
-           Loss of oil seal (faulty or worn ‘O’ rings)
-           Insufficient back pressure

WATERTIGHT BULKHEAD

Function
-           Divide ship into watertight compartment & thus restrict the volume of water, which may enter the ship if the shell plating damaged.
-           Separate different type of cargo & to divide tanks & machinery spaces from cargo spaces.
-           In the event of fire, it reduces largely the rate of spread.
-           Increase transverse strength of the ship
-           Reduce vertical deflection when the compartments are full of cargo.


WATERTIGHT DOOR
  
-           It fitted to any access opening in a watertight bulkhead.
-           Openings must only be cut where necessary for the safe working of the ship.
-           Kept as small as possible, 1.4 m high and 0.75m wide being usual.
-           Material mild steel, cast steel or cast iron.
-           Hinged, vertical, and sliding type of watertight door.
-           Hinged type not permitted below waterline.
-           Good sealing
-           To equivalent strength to unpierced bulkhead .
-           Sliding door may be hand controlled.
-           It has an indicator at above deck operating position showing if they are open or closed.
-           There must be no groove at the bottom door to collect dirt, which prevent door from closed.
-           Must have rubber packing around the door.
-           Solas requirement stipulated that they be capable of  being  operated when ship listed 15°, and be opened and closed from a position above the bulkhead deck or locally .









No comments:

Post a Comment